• Pure Sinewave
Output
• Small Size & Light Weight for Portability
• High reliability
• OV, O.L. and O.T. protected
• MTTR below 30 minutes; modular design
• Withstands high reactive load
• Tight voltage and frequency regulation
• Output fault alarm (relay closure)
• All boards conformal coated with Acrylic MIL-I-46058 Type R.

•
Special output voltages and frequencies
•
Provision for 3 Phase connection with 2 more identical
units
•
19" Panel mount or wall mount plates
•
Alternative connectors
•
Custom painting and marking
•
Transfer switch to alternate AC source
•
Non-PVC wiring
|
|

Electrical
Input Voltage: 20-32 VDC per MIL-STD-1275
Output Voltage: 120VAC (220VAC optional)
Frequency: Choose 50 Hz, 60 Hz, or 400 Hz (+/-0.5%)
Frequency Regulation: +/-0.5% N.L. to F.L.
Voltage Regulation: +/-1.5% N.L. to F.L.
Efficiency: Approximately 85-86% (depending on model)
Reactive Load: 0.75 Lead to 0.75 Lag
Distortion: 5% THD, 3% Single Harmonic
Overload: 125% for 5 minutes
Overload Protection Range: Automatic
overload & short circuit protection
Sync & Phase Lock Range:
+/-3 Hz, Typical (50/60 Hz models)
Transient Response: Approx. 1/4
cycle recovery to 95% of nominal
TYPICAL
Operating Temp: -32°C to +50°C per MIL-STD-810 (extended range available)
Storage Temp: -33°C to +71°C per MIL-STD-810
Rain & Dripping Water: to MIL-STD-810F Method 506.4
Vibration: per MIL-STD-810F Method 514.5 on iso-mount
Shock: per MIL-STD-810F Method 516.5 on iso-mount
Humidity: To 95% RH non-condensing per MIL-STD-810F Method 507.4 Fungus: to MIL-STD-810F Method 508.5
Salt / Fog: per MIL-STD-810 Method 509.4
Sand / Dust: per MIL-STD-810 Method 510.4
Altitude: to 15,000 feet per MIL-STD-810F Method 500.4
EMI: Designed to meet MIL-STD-461 CE102, CS101, CS114, and CS115 with optional external filter
Finish: CARC paint IAW MIL-DTL-53039B (Green 383)
|