NAVY GALAXY SERIES TRUE
ON-LINE UPS
|
This
rugged Navy Galaxy-Series UPS System is specifically
designed for submarine and shipboard applications
in compliance to MIL-STD-1399, MIL-STD-461,
MIL-STD-901, MIL-STD-167, MIL-STD-810, AND
MIL-STD-740. The example pictured is a compact
2.5 KVA unit built for use on the US Virginia
Class Submarine, as well as other high profile
shipboard and submarine applications in US
and US-friendly fleets worldwide. This model
has a three-phase power factor corrected (PFC)
input of 115 VAC L-L, 50/60 Hz per MIL-STD-1399
Section 300 Type I and a pure sinewave galvanically
isolated output of 115 VAC, Single-Phase.
Single-phase input is optional, and output
frequency is available in 50, 60, or 400 Hz
(specify.) This UPS System contains all of
the features standard on other Galaxy-Series
units, as well as additional features that
make it ideal for Naval applications. |
|

|
Mec.Outline
Drawing Click Here 
PDF Data
Sheet Click Here  |
RUGGED
TRUE ON-LINE UPS
NAVY GALAXY SERIES
Model Selection
NGRS11-1.5K60-115-115 |
1.5 |
115VAC |
115 VAC |
115 |
10 min |
NGRS11-1.5K60-115(D)-115 |
1.5 |
115VAC L-L |
115VAC |
115 |
10 min |
NGRS11-2.5K60-115-115 |
2.5 |
115VAC |
115VAC |
125 |
10 min |
NGRS11-2.5K60-115(D)-115 |
2.5 |
115VAC L-L |
115VAC |
125 |
10 min |

• Single
Phase Input
• RS 232 Interface
• RUPS 2000 Computer Interface
• Chassis Slides
• MS Connectors Mates
• High Speed Mechanical Transfer Switch
• Custom Paint & Markings
|
|

ELECTRICAL
Optional Input Voltages available (select):
115, 120, 208, 220, 230, 240 VAC. 1Ø
115/200, 120/208, 220/380 3Ø
Optional Input Frequencies available (specify): 50, 60 or 400 Hz
Optional Output Voltages Available (specify): 115, 120, 208, 220, 230, 240 VAC 1Ø
Output Frequency (specify): 50, 60 or 400Hz
Voltage Regulation: +/-
2% NL to FL
Frequency Regulation: 0.1%
Harmonic Distortion: 2%
THD Typical
5% Max
Input Power Factor: 0.99
Efficency at full load: 82%
typical
Overload: 125% for 5 minutes
INTERNAL BATTERIES
Premium 10 year life wide temp batteries
which are sealed, maintenance free,
and user replaceable.
PROTECTIVE FEATURES
AC & DC Input Circuit Breakes, Low
Battery Shut Off, Overload and Thermal
Protection, Audible Alarm with Silence
Switch, and EPO.
ENVIRONMENTAL
Operating Temperature: 0° to
+50° C per MIL-STD-810D
Storage Temperature Range: -30° to
+60° C
Humidity: to
95% non-condensing
Elevation: 15,000
Ft. (4.572m) operating
Audible noise: Less
than 55 dBA at 5 ft. (1.5 m)
Cooling: Forced air (exhaust at rear) Airflow 200 CFM Maximum
EMI: Per MIL-STD-461B/E
Vibration: Per
MIL-STD-167-1
Shock: 20g for
20ms half sinewave per MIL-STD-901C
Grade A
Structureborne Noise: MIL-STD-740B
Grade A
ALARMS AND DIAGNOSTICS
System Status: Green/Red
Utility Off: Red
UPS Off: Red
Low Battery: Red
Logic Fault: Red
Alarm Contacts: Standard
RS 232: Optional
UPS Overload: Red
Over-Temperature: Red
Load on Utility: Red
(with XFR SW option)
|
SYSTEM COMPLIANCE
Additional Ruggedization to meet MIL-STD-901,
MIL-STD-167, and MIL-STD-810: The
UPS System’s construction is extremely
robust, and ruggedized throughout. All components
and modules within the unit are mounted
using additional steel brackets and heavy-duty
stainless-steel hardware, which is then
further secured using Loctite and RTV where
required. All boards are conformal-coated
(Acrylic MIL-I-46058 Type R) for maximum
resistance to potential condensation and
fungus growth. The unit was tested and qualified
as follows:
MIL-STD-901C for Grade A, Class
II Equipment: Shock test with half sinewave,
20ms duration, 15g peak acceleration shock
pulse.
MIL-STD-167-1 for Type I Equipment:
Vibration test with range of 4 Hz low frequency
to 33 Hz high frequency.
MIL-STD-810D: Operating Temperature
Tests including High Temperature Test per
Procedure II, Method 501.2, Table 501.2-II
Ambient Air, 4 Cycles @ 24 Hours per cycle,
Low Temperature Test per Procedure II, Method
505.2, Table 505.2-I Region CO, 4 Cycles
@ 24 Hours per cycle, and Temperature Shock
Test per Procedure I, Method 503.2, between
0-40 degrees Celsius, 4 Cycles @ 24 Hours
per cycle.
Internal EMI Reduction Package to meet MIL-STD-461:
The design of this unit is specifically
focused on reducing EMI emissions. The UPS
contains substantial internal filtering
to minimize EMI emissions. Inputs which
may be susceptible to transients are protected
by several methods, including MOVs. All
internal magnetics are shielded with copper
and mu-metal to further minimize emissions.
The compact rack mount chassis (5.25”
High x 19” Wide x 24.125” Deep)
is specifically treated with low surface
resistivity finishes on the interior. All
aluminum parts are treated with clear irridite.
The steel parts are treated with zinc plate,
followed by a clear chromate. All exterior
portions (except for mating surfaces) are
then painted with glossy ANSI-61 gray to
assure excellent bonding of mating sheet
metal parts. All input and output ventilation
filters include metal honeycomb-style filters.
The unit was tested and qualified as follows:
MIL-STD-461B Part VI for EMI Class A5: CE01,
CE03, CS01, CS02, CS06, CS09, RE01, RE02,
RS01, RS02, RS03.
Super-Rugged, Long Life Hawker
Energy Batteries: Internal Hawker
Energy sealed, maintenance free batteries
provide 10 minutes back up time at full
load. These batteries are extremely resistant
to shock, vibration, and wide temperature
ranges. Also, they have a very long service
life (8-10 years measured at 25 degrees
Celsius ambient temperature) for a minimum
of maintenance. The batteries are user replaceable.
Structureborne and Airborne Noise:
The rugged Navy Galaxy-Series UPS System
was tested and qualified to MIL-STD-740B
for Grade A Type III Equipment.
Pressure Tests for Submarine Usage:
The Navy Galaxy Series UPS System was tested
to atmospheric pressure within the range
of 750-1250 millibars, and maintained standard
operation to specification to the following
test pressures for 1 hour:
250 millibars above ambient (applied within
30 seconds and released within 30 seconds)
250 millibars below ambient (applied within
30 seconds and released within 30 seconds)
Ambient pressure of 1000 millibars
Some of the features shown above can be
incorporated on our standard UPS models
– Nova Electric offers Rugged UPS
Systems for Naval Applications in all of
our standard rack-mount packages, from 1-6+
KVA. We can also incorporate these additional
features on our DC-AC Inverters and Frequency
Converters as well. If you have a unique
submarine or shipboard application that
calls for a rugged AC power source, please
don’t hesitate to contact us –
we have over 38 years of experience designing
and manufacturing America’s best power
conversion equipment for harsh environment
applications!