Ruggedization against high shock, vibration, and
humidity
• MS connector mates
• 400 Hz input and / or output
• Chassis slide
guides
• Solid state or electromechanical transfer switch
• Additional battery back-up time
(up to 24 hours available)
• Premium batteries with up to 10 year life
• Custom Paint
• Custom Enclosures
|
|

Input
| Voltage
(select): |
115, 120, 208,
220, 230, 240 VAC 1Ø
115/200, 120/208, 220/380
3Ø |
Input voltage autoselect available, consult factory
Frequency: 50 Hz, 60 Hz, and 400 Hz available
Dual input frequency available consult factory
Connections:
MS connector (mates optional)
Output
Voltage (specify): 115,120, 208, 220, 230, 240 VAC, 1Ø
Frequency: 50 Hz, 60 Hz, and 400 Hz available
Voltage regulation: +/-2% no load to full
load
Dynamic voltage regulation: +/-10% for 100%
load change
Frequency regulation: +/-0.5% no load to
full load (Free running)
Connections: MS connector (mates optional)
Load power factor: 0.7 lead to 0.7 lag
Harmonic distortion: 5% THD
Efficiency at full load: 85-87% AC-AC
Typical
Nominal Dimensions
3 KVA UPS Dimensions: 5.25" High x 19" Wide x 22.25" Deep
3U Battery Dimensions: 5.25"
High x 19" Wide x 22" Deep
4U Battery Dimensions 7" High x 19" Wide x 24" Deep
| Overload: |
125% for 10 minutes 1000%
for one cycle
(Via optional transfer switch) |
MTBF: 30,000 hours per MIL-HDBC-217 (ground fixed, 25 °C)
MTTR: 30 minutes with qualified personnel
Environmental
Ambient operating temperature range:
-20° to +50° C*
Storage temperature range: -40° to +60°
C*
Humidity: to 95% RH non-condensing – Designed
to meet MIL-STD-810. All boards conformal coated
with Acrylic MIL-I-46058 Type AR.
Shock: 20g, 11 mS half sinewave – Designed
to meet MIL-STD-810 optionally
EMI: Designed to meet FCC Part 15, Class
A. Designed to meet MIL-STD-461 with optional
additional filtering.
*For best results, batteries
must be kept at 25 degrees Celsius ambient temperature.
Extreme low temperatures will result in reduced
run time, while extreme high temperatures result
in significantly reduced battery lifespan. Click
here for more information on THE
EFFECTS OF EXTREME TEMPERATURES ON BATTERIES.
Elevation:
15,000
ft. (4,572 m) operating**
40,000
ft. (12,192 m), non-operating**
**For batteries, please follow battery
manufacturer instructions regarding recommended
elevation parameters.
Audible noise:
Less than 55 dBA at 5 ft. (1.5 m)
Transportation
and handling :
MIL-STD-810C
Protective Features
Circuit Breakers: Battery
Charger Input, Battery Input
Fuses: Inverter Input, AC Bypass Input (if optional transfer switch is supplied)
Low Battery Shut Off
Overload Protected
Thermal Protection
Output Short Circuit Protection
Transient Protection (available to MIL-STD-1399
Audible Alarm with Silence Switch
RS 232
This model includes bi-directional RS 232 as a standard feature
Standard Remote
Contacts
Major Alarm: Logic Fault, Low Battery, Over-Temperature,
UPS Off, UPS Overloaded
Minor Alarm: Utility Off, Load on Utility
Standard
Front Panel Diagnostics
System Status: Green/Red
Utility Off: Red
UPS Off: Red
Low Battery: Red
Logic Fault: Red
UPS Overload: Red
Over-Temperature: Red
Load on Utility: Red |