Jupiter Series

120/208 VAC, 60 Hz, 3 Phase
ETL CERTIFIED TO UL 1778

10 – 60 KVA Pure Sinewave UPS

Nova’s Jupiter-Series UPS Systems are high-reliability power sources specifically designed for demanding commercial, heavy industrial, and military applications. They can be built to meet MIL-STD-810, MIL-S-901, MIL-STD-461, and other standards optionally. Please refer to the standard series here. These models utilize True On-Line technology and the most durable components, offering maximum field-proven reliability for severe environment and high reliability applications.

Standard ETL Model Selection

etl-small

60 Hz Models
Model KVA KW In / Out (VAC) Dimensions (HxWxD) UPS Weight (Kg / Lbs) Battery Run Time (Min.) Battery Dimensions (HxWxD) Battery Weight (Kg. / Lbs.)
JE11-10K3/6-120/208-120/208-10M 10 8 120/208 63" x 22" x 31.5" 300 / 660 HR1234 12V 29pcs 10 Internal 85 /187
JE11-10K3/6-120/208-120/208-20M 10 8 120/208 63" x 22" x 31.5" 300 / 660 HR1234 12V 58pcs 20 Internal 170 / 374
JE11-15K3/6-120/208-120/208-5M 15 12 120 / 208 63" x 22" x 31.5" 341 / 750 HR1234 12V 29pcs 5 Internal 85 / 187
JE11-15K3/6-120/208-120/208-15M 15 12 120 / 208 63" x 22" x 31.5" 341 / 750 HR1234 12V 58pcs 15 Internal 170 / 374
JE11-20K3/6-120/208-120/208-10M 20 16 120/208 63" x 22" x 31.5" 400 / 880 HR1234 12V 58pcs 10 Internal 170 / 374
JE11-30K3/6-120/208-120/208 30 24 120/208 63" x 22" x 31.5" 470 / 1034 12V 26AH 29pcs 9 63"x22"31.5" 410 /900
JE11-30K3/6-120/208-120/208 30 24 120/208 63" x 22" x 31.5" 470 / 1034 12V 26AH 58pcs 24 63"x22"31.5" 690 /1520
JE11-30K3/6-120/208-120/208 30 24 120/208 63" x 22" x 31.5" 470 / 1034 12V 75AH 29pcs 29 63" x 43.5" x 31.5" 1020 / 2245
JE11-40K3/6-120/208-120/208 40 32 120/208 63" x 22" x 31.5" 530 / 1166 12V 26AH 29pcs 7 63"x22"31.5" 410 / 900
JE11-40K3/6-120/208-120/208 40 32 120/208 63" x 22" x 31.5" 530 / 1166 12V 26AH 58pcs 18 63"x22"31.5" 690 / 1520
JE11-40K3/6-120/208-120/208 40 32 120/208 63" x 22" x 31.5" 530/ 1166 12V 75AH 29pcs 23 63" x 43.5" x 31.5" 1020 / 2245
JE11-50K3/6-120/208-120/208 50 40 120/208 63" x 22" x 31.5" 560 / 1232 12V 26AH 58pcs 13 63"x22"31.5" 690 / 1520
JE11-50K3/6-120/208-120/208 50 40 120/208 63" x 22" x 31.5" 560 / 1232 12V 75AH 29pcs 16 63" x 43.5" x 31.5" 1020 / 2245
JE11-60K3/6-120/208-120/208 60 48 120/208 63" x 22" x 31.5" 630 / 1386 12V 26AH 58pcs 9 63"x22"31.5" 690 / 1520
JE11-60K3/6-120/208-120/208 60 48 120/208 63" x 22" x 31.5" 630 / 1386 12V 75AH 29pcs 13 63" x 43.5" x 31.5" 1020 / 2245

Note: Any UPS can be used with larger batteries to obtain higher run times. 75AH, 88AH and 100AH batteries are also available. Consult factory for run times.

 STANDARD FEATURES

  • • Complete input to output ‘Galvanic’ isolation.
  • • High frequency almost silent operation
  • • Push button starting and stopping
  • • Diagnostic panel with LCD and LED display
  • • Soft start on inverter
  • • Overload & and short circuit protection on charger and inverter
  • • Maintenance free batteries
  • True On-Line operation
  • • Solid state transfer switch built in and standard at no additional charge
  • • Maintenance bypass switch built in and standard at no additional charge
  • • All electronics are built in modular front access and front removable sub assemblies for easy service and maintenance
  • • Batteries may be built into units up to 20 KVA
  • • Automatic dual rate battery charger (float charge and boost charge)
  • • FCC class A approved
  • • Remote isolated dry relay contacts

 MONITORING FEATURES

  • The unit includes an RS232 communication option called UPSCOM. This is an RS232 connection to a PC that can monitor the output parameters and any abnormal conditions that have occurred in real time. Standard commercially available software is required. The RS232 Feature is included at no additional charge.

 FRONT PANEL LCD DISPLAY AND LED INDICATORS

  • This will report all UPS parameters including input and output voltages, currents, frequency, battery voltage, battery current, and many other functions.

 LCD DISPLAY

  • Real time status, data, and historical events are displayed via the LCD display. The UPS parameters, real-time clock, inverter, and buzzer can also be set through this LCD, which is backlit by LEDs for visual clarity.

 STATUS LEDs

LEDs representing all important operational information provide feedback to the user. LED descriptions are as follows:

  • UPS ON – UPS is running normally.
  • UPS SS – UPS static switch is on while the reserve static switch is opened (off).
  • SHORT CIRCUIT – UPS output is in short circuit state.
  • FUSE / OVERTEMP SD – UPS has shut down due to either fuse open or over temperature.
  • UPS FAIL SHUTDOWN – UPS has shut down due to low inverter AC output voltage.
  • BYPASS ON SHUTDOWN –UPS shut down due to closed bypass breaker. UPS shut down due closed bypass breaker (while inverter running).
  • HIGH DC SHUTDOWN – UPS shut down due to high DC bus.
  • OVERLOAD SHUTDOWN – UPS shutdown due to overload of the inverter for a period greater than the inverter can accept. The UPS will start after 7 seconds.
    70% LOAD – load connected to the output is over 70% of the Inverter rating.
    110% LOAD – load connected to the output is over 110% oh the Inverter rating.
    125% LOAD – load connected to the output is over 125% of the Inverter rating.
    150% LOAD – load connected to the output is over 150% of the Inverter rating.
  • RESERVE AC FAIL – reserve AC magnitude is out of range.
  • RESERVE FREQ FAIL – reserve frequency is out of range.
  • BATTERY LOW – DC bus (or battery) is lower than specified range, low battery shutdown will occur soon.
  • BATTERY LOW SHUTDOWN – inverter shutdown due to DC bus (or battery) lower than the acceptable DC voltage of the inverter.
  • HIGH DC – DC voltage over the acceptable DC voltage of the inverter.
  • EMERGENCY STOP – Inverter shut down activated by emergency stop switch.
  • DATA LINE – Blink when data is transmitted to or received from the communication port

 OTHER OPTIONS

  • DC INPUT BREAKER OPTION / BATTERY FUSE
    The optional DC Input breaker disconnect or fuse is offered to provide protection for the DC Battery connection. One or the other must be ordered.
  • TURN ON SERVICE OPTION
    We offer a turn on service that will ensure the UPS has been properly installed and the full warranty is in effect (failures caused by incorrect installation are not covered by the warranty.) If this option is selected, the customer will also automatically receive an additional 3 months added to the warranty at no additional charge.
  • SPARE PARTS KIT OPTION
    We offer a spare parts package that includes one of each board, spare fuses, spare semiconductors, and spare fans. These spare part kits are priced lower when ordered with the initial order then if they are ordered later on.

 WARNING LEDs

When abnormal condition occurs, these LEDs will light to warn the user of the cause of the fault condition. Therefore all these LEDs are off under normal condition. These LEDs are:

  • RESERVE FAIL – Reserve AC input is abnormal either due to AC magnitude out of range or frequency out of range.
  • FUSE/TEMP – Either inverter fuse is open or over temperature has occurred.
  • OVERLOAD – Output is overloaded by over 110%, 125% or 150%
  • HIGH DC – This LED will light when DC input approaches high-line limit.
  • BAT LOW – This LED will light when the DC voltage is low.
  • BAT LOW STOP – This LED will light when the DC voltage is lower than specified range.
  • FAULT – The inverter is off due to abnormal conditions such as overload, short circuit, high DC, fuse over temperature, bypass breaker on emergency stop.

Since these LEDs are located behind the transparent window, the user can use them clearly without opening the door.

 AUDIBLE ALARM

The audible alarm will beep under either one of the following conditions:

  • INVERTER IS OVERLOADED
    > 110% beep once every 3 seconds
    > 125% beep once every second
    > 150% beep twice every second
  • INVERTER IS SHORT CIRCUITED – Beeps continuously
  • FUSE OPEN– Beeps continuously
  • HEAT SINK OVER TEMPERATURE – Beeps continuously
  • HIGH DC SHUTDOWN – Beeps continuously
  • BYPASS ON STOP – Beeps continuously
  • EMERGENCY ON STOP – Beeps continuously
    The buzzer will also beep once every time the inverter is switched on or off to acknowledge to the user that his key entry is valid and accepted.temperature, bypass breaker on emergency stop.

Since these LEDs are located behind the transparent window, the user can use them clearly without opening the door.

 COMMUNICATIONS OPTIONS

We offer options for communications with this Inverter series. Some popular options available at additional cost include the following:

  • UPSCAN: This is a hand held remote display and control module with LCD and LED display that can monitor via RS-485 UP to 99 UPS Units at a remote distance of up to 3,000 feet.
  • NETAGENT: This provides capability to monitor the Inverter over the internet. It includes the appropriate additional SNMP card and microprocessor. The software required is provided by MEGATEC at additional cost.
Specifications for the Nova Jupiter 3 Phase UPS Series
PHASE 3-Phase Input/ 3-Phase Output
KVA 10 15 20 30 40 50 60
Input Rectifier
Input Voltage (VAC) 120/208 VAC
Input Range +/- 20% (>+20% is available upon request)
Input Frequency 50/ 60 + 5Hz
Power Walk In 0% – 100% :20 sec
Voltage Regulation 1%
Efficiency 98%
Rectification Type 6 Pulse Standard, 12 Pulse Optional
Battery
Battery Type Maintenance free lead-acid batteries/ 12V (348 VDC Nominal)
Maximum Charge Current(Adc Selectable)LO,MED,HI 4 8 8 12 16 25 26
Battery Start Yes, UPS can be started without AC source.
Inverter
Output Voltage (VAC) 120/208
Wave Form Sinewave
Output Power Factor 0.8
Frequency Lock Range 50 / 60 Hz +/- 3 Hz
Output Frequency (Free Running) 50 / 60 Hz +0.1Hz (crystal controlled)
Output Frequency (free running) 0.7 lead to lag
Phase Shift Under 100% Unbalanced Load <0.5%
THD (Linear Load) < 2%
Overload
<110% Continuous
>110-125% Up to 15 minutes
>125-150% Up to 5 minutes
>150-170% Up to 30 seconds
>170-200% Up to 15 seconds
Efficiency (100% Load) 93% 93% 93% 93% 93.5% 93.5% 94%
STATIC SWITCH
Voltage Range Same as Main Rectifier Input.(Different voltages are available upon request)
Mains <-> Inverter 0 ms (True Online)
Overload As per inverter rating plus >200% to 300% = 1 second
OVERALL CHARACTERISTICS
Overall Efficiency 91% 91% 91% 91% 91.5% 92% 92%
Maximum Heat Dissipation (kw) 0.7 1.1 1.4 1.9 2.6 3 3.5
BTU/h @ Full Load 2.4K 3.6K 4.8K 6.5K 8.9K 10.3K 12K
Audible Noise <65 dBA (at 1m)
Temperature 0-40ºC (32-104ºF)(Other ranges available)
Humidity 0%-95% (Non-condensing)
Altitude <1500 m Above Sea Level
MTTR Less Than 30 minutes
EN50091-1, -2 Yes
Short Circuit Protection Yes
MTBF As per Field Experience >100,000 Hours for loss of AC Output
Lightning / EMC Filter MOV / Input & Output ( FCCCLASS A)
Galvanic Isolation Input and Output True Galvanic Isolation
LED, LCD, Audible Alarm Yes
Remote Control/ Communication Interface Monitoring 1~99
Units simultaneously / Dry Contact, RS-232, RS-485 (Optional)
The appearance of U.S. Department of Defense (DoD) visual information does not imply or constitute DoD endorsement.