CGD Series 1.5 KW Parallelable and Three-Phase Configurable COTS Inverters
- Included built-in automatic transfer switch (ATS) with AC input circuit breaker
- Parallelable for increased power
- 3 phase WYE configurable
- 120/240 CT split phase configurable
- Microprocessor based design with absolutely
accurate and stable frequency. - Compact and light weight, yet rugged and
vehicle rated. - Tightly regulated output voltage and frequency
- Switch selectable 50 or 60 Hz output, all models
- Capable of driving highly reactive loads such as
electric tools and appliances. - Capable of driving highly capacitive loads such
as switching power supplies. - Very low harmonic distortion
- Suitable for vehicle or wall mounting
- Standard outputs 110V/60Hz, 230V/50Hz
- Switch selectable ±10V output change
- RS-232 communication (RJ11 Connector)
- Description
- Models
- Specifications
- Data Sheets
Description
Nova Electric’s CGD-Series inverters are intended for commercial and industrial applications wherever pure sinewave power is needed at 50 or 60 Hz. These inverters are ideal for running electronic loads such as computers, monitors, printers, telecom systems, radios, fluorescent lamps from batteries, field generators, and solar electro-voltaic panels. They can also drive hand drills, motors and small compressors – please consult the factory for proper sizing. These CGD models can also be optionally ruggedized against shock, vibration, and humidity for military applications including vehicle mounted, shipboard, submarine, aircraft, and ground fixed shelters.
- Included built-in automatic transfer switch (ATS) with AC input circuit breaker
- Parallelable for increased power
- 3 phase WYE configurable
- 120/240 CT split phase configurable
Applications:
- Computers
- Sail Boats
- Appliances
- Printers
- Photo Voltaic Instruments
- Monitors
- Electric Tools
- RVs
CGD1.5K-12-120 | CGD1.5K-24-120 | CGD.5K-48-120 | CGD1.5K-12-220 | CGD1.5K-24-220 | CGD1.5K-48-220 |
|
---|---|---|---|---|---|---|
No Load Power Consumption On Mode @ Save Mode On Mode @ No Load Mode | @12VDC 0.9A <2.4A | @24VDC 0.35A <1.2A | @48VDC 0.3A <0.6A | @12VDC 1.1A <3.3A | @24VDC 0.7A <1.6A | @48VDC 0.4A <0.8A |
Fuse | 40A x 6 | 20A x 6 | 15A x 4 | 40A x 6 | 20A x 6 | 15A x 4 |
BAT. Low Alarm ±3% | 10.5 VDC | 21.0 VDC | 42.0 VDC | 10.5 VDC | 21.0 VDC | 42.0 VDC |
BAT. Low Shut-down ±3% | 10.0 VDC | 20.0 VDC | 40.0 VDC | 10.0 VDC | 20.0 VDC | 40.0 VDC |
BAT. Low Restart ±3% | 12.5 VDC | 25.0 VDC | 50.0 VDC | 12.5 VDC | 25.0 VDC | 50.0 VDC |
BAT. High Alarm ±3% | 15.5 VDC | 31.0 VDC | 62.0 VDC | 15.5 VDC | 31.0 VDC | 62.0 VDC |
BAT. High Shut-down ±3% | 16.0 VDC | 32.0 VDC | 64.0 VDC | 16.0 VDC | 32.0 VDC | 64.0 VDC |
BAT. High Restart ±3% | 15.0 VDC | 30.0 VDC | 60.0 VDC | 15.0 VDC | 30.0 VDC | 60.0 VDC |
Model Selection
- Input Voltage: See Model Table
- Output Voltage 110V model: 100/110/120 VAC
- Output Voltage 220V model: 220/230/240 VAC
Output Frequency: 50 or 60 HZ ±0.1% Accuracy - Continuous Power Rating: 1500W/1500VA
- Peak Power (3 seconds): 1800W
- Surge Rating: 2400W
- Efficiency: 88% (12V), 89% (24V), 90% (48V)
Output Waveform Sinewave: <3% THD* - Output Voltage Regulation: ±3%
- Protection: Overload, Short Circuit, Reverse Polarity (Fuse), O.T, Over/Under Input Voltage, Fan Failure
- Output Frequency Regulation: ±0.1%
- Synchronous Frequency: 47-57 / 53 – 63 Hz
- ATS: Inverter to utility AC < 5ms. Utility AC to inverter: < 10 ms.
SAFETY & EMC
- 120V: FCC Class B
- x220V: EN55014-1**, EN55014-2**; EN61000-3-2, -3-3; EN61204-3;
ENVIRONMENTAL
- Operating Temp.: -20° to +40°; +60°C @ 40% Power Load
- Storage Temp. Range: -40° to +71°C
- Humidity: To 90% non-condensing
COMMUNICATION PORT
- RS232 (RJ-11 type connector) / Ethernet optional
INDICATORS & OPTIONS
- Input level, Fault Status
- Optional Remote Control
- Optional Ethernet Communications
NOTES
* Under condition:> 1.15 x rated VDC, 110V or 230V / linear load
** EN55014-1, EN55014-2 Class B: output cable less than 6.5 ft (2 meters)