GLFC Series 1.5-4.5 KVA Rack Mount Solid-State Three Phase Frequency Converters
- Solid-State Design
- Pure Sine Wave Output
- Extremely Rugged Construction Suitable For Harsh Environments
- High Reliability – MTBF Exceeds 100,000 hours
- Overload, Overvoltage, and Overtemp Protected
- MTTR below 30 minutes
- Transformer-Isolated For High Inrush Loads
- Withstands Highly Reactive Load
- Tight Voltage and Frequency Regulation
- Custom Voltages and Frequencies Available
- Conformal Coated PCBs and All Stainless Hardware
- Description
- Models
- Specifications
- Popular Options
- System Compliance
- Videos
- Data Sheets
Description
Nova frequency converters are high-reliability power sources specifically designed for demanding applications in high shock, vibration, humidity, and EMI environments. They can be built to meet MIL-STD-810, MIL-STD-167, MIL-S-901, MIL-STD-1472, MIL-STD-461, and other standards optionally. These models are especially suitable for severe environment and high reliability applications such as:
- Military Applications: HMMWV, UAV, Shipboard, Submarine, Aircraft and Mobile Power Units, Shelters
- Aircraft Power
- Communications Systems
- Cellular Sites
- European Power / Export Testing
- Power Conditioning & Frequency Stabilization
- U.S. Power Abroad
- Railroad Signaling Power
Partial Model Selection - Replace "XX" Shown In Model No. With Desired Nominal Input Voltage (e.g., 120, 120/208, 220, 220/380, 115, 115/200, etc.)
PARTIAL MODEL NO. | KVA | KW | OUTPUT VOLTAGE | OUTPUT FREQUENCY (Hz) | WEIGHT | SIZE (HxWxL) | OUTLINE DRAWING | |
---|---|---|---|---|---|---|---|---|
GLFC1.5K3/5-XX-220/380 | 1.5 | 1.2 | 220/380 | 50 | 96 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC1.5K3/6-XX-120/208 | 1.5 | 1.2 | 120/208 | 60 | 96 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC1.5K3/4-XX-115/200 | 1.5 | 1.2 | 115/200 | 400 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC2K3/5-XX-220/380 | 2 | 1.6 | 220/380 | 50 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC2K3/6-XX-120/208 | 2 | 1.6 | 120/208 | 60 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC2K3/4-XX-115/200 | 2 | 1.6 | 115/200 | 400 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC3K3/5-XX-220/380 | 3 | 2.4 | 220/380 | 50 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC3K3/6-XX-120/208 | 3 | 2.4 | 120/208 | 60 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC3K3/4-XX-115/200 | 3 | 2.4 | 115/200 | 400 | 118 | 5.25” x 19” x 22.5” | QUOTE | |
GLFC4.5K3/5-XX-220/380 | 4.5 | 3.6 | 220/380 | 50 | 130 | 8.75” x 19” x 24” | QUOTE | |
GLFC4.5K3/6-XX-120/208 | 4.5 | 3.6 | 120/208 | 60 | 130 | 8.75” x 19” x 24” | QUOTE | |
GLFC4.5K3/4-XX-115/200 | 4.5 | 3.6 | 115/200 | 400 | 130 | 8.75” x 19” x 24” | QUOTE |
- Power Ratings: 1.5KVA – 4.5KVA
- Input Voltage: Most standard AC voltages including 115, 120, 200, 208, 220, 240, 277, 380, and 480 available in single and three-phase configurations. Power Factor correction available on selected GLFC-Series models.
- Output Voltage: Most standard three phase AC voltages including 120/208, 115/200, 220/380, and 277/480
- Frequency: 50 Hz, 60 Hz, or 400 Hz (+/-0.5%)
- Frequency Regulation: +/-0.5% N.L. to F.L. (Crystal available)
- Frequency Transients: None
- Voltage Regulation: +/-1.5% N.L. to F.L.
- Efficiency: Approximately 85-95% (depending on model)
- Total Harmonic Distortion: 3% Typical, 5% Max
- Overload: 120% Typical Power Factor: 0.7 Lead to 0.7 Lag
- Input Circuit Protection: Circuit Breaker / Fuses, Transient Suppressors Output
- Circuit Protection: Current Limit, Short Circuit Protection, Thermal Protection, and Semi-Conductor Protection
- Phase Rotation: Any (three-phase models)
ENVIRONMENTAL & MECHANICAL
- Operating Temp:
-20°C to +50°C Standard
-40°C to +71°C Optional (on selected models) - Cooling: Forced Air by internal fan
- Vibration: Normal shipping and handling
- Shock: 20g, 11 mS half sinewave – Designed to meet MIL-STD-810 optionally
- Elevation: 10,000 ft. typical
- Humidity: to 95% RH non-condensing – Designed to meet MIL-STD-810. All boards conformal coated with Acrylic MIL-I-46058 Type R.
- Audible Noise: 65 dBA at 5 ft. typical
- EMI: Designed to meet FCC Part 15, Class A. Designed to meet MIL-STD-461 with optional additional filtering.
- MTBF: 30,000+ hours typical per MIL-HDBK-217
- MTTR: Less than 30 minutes.
OPTIONS
- Ruggedization against high shock, vibration and humidity
- MS connector mates
- Multiple output outlets
- Chassis Slide Guides
- Rugged Transit Cases and Custom Enclosures
- 400 Hz input and / or output
- CAD Free Connectors
- Non-PVC wiring
- High IP Protection for front / rear panels (typically IP32,) including louvers on all intake and exhaust, as well as fully gasketed breakers, switches, and indicators.
- AUX DC Outputs
- Input Volt and Amp Meter Set (available on select models)
- Elapsed Time Meter (available on select models)
- Power Distribution Units (PDUs)
- Environmental Stress Screening Services